Unidrive M702 / HS72 Control Getting Started Guide 45
Issue Number: 4
Safety information Introduction Control connections Getting started
Basic parameters
(Menu 0)
Running the motor Further information
6.2.6 Use of the motor database for a Leroy Somer LSRPM motor for use in
RFC-S Sensorless mode.
Select ‘Motor Setup’ from the ‘Dashboard’.
On the ‘Motor Setup’ screen, select ‘Choose a motor’.
Select the required motor database:
Check
Saliency
In sensorless mode, when the motor speed is below Pr 00.045 / 10, a
special low speed algorithm must be used to control the motor. There
are two modes available, with the mode chosen based on the saliency of
the motor. The ratio No-load Lq (Pr 00.056) / Ld (Pr 05.024) provides a
measure of the saliency. If this value is > 1.1, then Non-salient mode
must be used (this is the default), otherwise Injection mode may be
used. Set Pr 00.054 for the selected mode: Injection (0) or Non-salient
(1).
Save
parameters
Select 'Save Parameters' in Pr mm.000 (alternatively enter a value of
1000 in Pr mm.000) and press red reset button or toggle the
reset digital input.
Run Drive is now ready to run