Unidrive M400 Quick Start Guide 37
Issue Number: 8
This parameter controls access via the drive keypad as follows:
This parameter changes the functions of the input terminals which are normally associated with the
enabling, starting and stopping the drive.
Action will only occur if the drive is inactive. If the drive is active, the parameter will return to its pre-
altered value on exit from edit mode.
Can be set to zero to change the logic for DI/O1-7 to negative logic, so that the state parameter is 0 if
the digital I/O is high or 1 if the digital I/O is low.
00.010 User Security Status
RW Num ND NC PT US
OL
Level 1 (0), Level 2 (1),
All Menus (2), Status Only (3),
No Access (4)
Level 1 (0)
RFC-A
Value Text Function
0 Level 1 Access to first 10 parameters in Menu 0 only.
1 Level 2 Access to all parameters in Menu 0.
2 All Menus Access to all menus.
3 Status Only
The keypad remains in status mode and no parameters can be
viewed or edited.
4 No Access
The keypad remains in status mode and no parameters can be viewed or
edited. Drive parameters cannot be accessed via a comms/fieldbus interface
in the drive or any option module.
00.011 Start/Stop Logic Select
RW Num US
OL
0 to 6
5
RFC-A
Pr 00.011 Terminal 11 Terminal 12 Terminal 13 Latching
0 User programmable Run Forward Run Reverse No
1 /Stop Run Forward Run Reverse Yes
2 User programmable Run Forward/Reverse No
3 /Stop Run Forward/Reverse Yes
4 /Stop Run Jog Forward Yes
5 User programmable Run Forward Run Reverse No
6 User programmable User programmable User programmable User programmable
00.012 Input Logic Polarity
RW Txt US
OL
Negative Logic (0) or
Positive Logic (1)
Positive Logic (1)
RFC-A