EasyManua.ls Logo

Nord Drivesystems NORDAC FLEX SK 225E Series - Potentiometers P1 and P2 (SK 2 X0 E Size 4 and SK 2 X5 E)

Nord Drivesystems NORDAC FLEX SK 225E Series
284 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Commissioning
BU 0200 en-3118 109
Pos: 23 9 /Anlei tung en/El ektr onik/FU und Star ter/4 . Inbe trieb nahme/ SK 1xx E, SK 2x xE, -FDS/Inbetriebnahme Gerät/ Poten tiom etern P 1 und P2 (S K 2x0E BG 4 und SK 2x5E ) [SK 2 xxE] @ 1\mod_1343222441209_388.docx @ 37549 @ 4 @ 1
4.3.2.4 Potentiometers P1 and P2 (SK 2x0E size 4 and SK 2x5E)
The setpoint can be set to a fixed value with the integrated potentiometer P1. Adjustment of the start-
up and braking ramps can be made via potentiometer P2.
Potentiometers
P2
P1
Potentiometers
P1 (continuous) P2 (stepped)
0 %
P102/103
P105
-
-
-
10 % 0.2 s 10 Hz 1 P102/103 P104
20 % 0.3 s 20 Hz 2 0.2 s 2 Hz
30 % 0.5 s 30 Hz 3 0.3 s 5 Hz
40 %
0.7 s
40 Hz
4
0.5 s
10 Hz
50 %
1.0 s
50 Hz
5
0.7 s
15 Hz
60 %
2.0 s
60 Hz
6
1.0 s
20 Hz
70 %
3.0 s
70 Hz
7
2.0 s
25 Hz
80 %
5.0 s
80 Hz
8
3.0 s
30 Hz
90 %
7.0 s
90 Hz
9
5.0 s
35 Hz
100 %
10.0 s
100 Hz
10
7.0 s
40 Hz
The function of P1 and P2 depends on DIP 4/5. The meaning changes according to the setting.
As standard, P1 sets the setpoint value of 0-100 % and P2 sets the ramp from 0.2-7 sec.
Pos: 24 0 /Allg emein/ Allg emeing ültig e Module/---------Seitenu mbruc h komp akt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1

Table of Contents

Other manuals for Nord Drivesystems NORDAC FLEX SK 225E Series

Related product manuals