EasyManua.ls Logo

Nord Drivesystems NORDAC FLEX SK 225E Series - 6.3 Messages

Nord Drivesystems NORDAC FLEX SK 225E Series
284 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NORDAC FLEX (SK 200E ... SK 235E)Users Manual for Frequency Inverters
226 BU 0200 en-3118
Pos: 64 2 /Anlei tung en/El ektr onik/FU und Star ter/6 . Meld ungen zum Betr iebsz usta nd/Mel dunge n @ 3\mod_1361803071259_388.docx @ 59851 @ 2 @ 1
6.3 Messages
Pos: 64 3 /Anlei tung en/El ektr onik/FU und Star ter/6 . Meld ungen zum Betr iebsz usta nd/Stör mel dung en (Tabel lenü bersc hrift) @ 3\mod_1361803456862_388.docx @ 59874 @ 5 @ 1
Error messages
Display in the
SimpleBox / ControlBox
Fault
Text in the ParameterBox
Cause
Remedy
Group Details in P700
[-01] / P701
Pos: 644 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ Fehl er E0 01 [ SK 1 80E/ SK 2 xxE /SK 5xxE/SK2xxE-FDS] @ 2\ mod_1347452921592_388.docx @ 46427 @ @ 1
E001
1.0 Overtemp. Inverter
"Inverter overtemperature"
(inverter heat sink)
Inverter temperature monitoring
measurements are outside of the permissible temperature
range, i.e. the error is triggered if the permissible lower limit
is undershot or the permissible upper temperature limit is
exceeded.
Depending on the cause: Reduce or increase the
ambient temperature
Check the FI fan / control cabinet ventilation
Check the FI for dirt
1.1 Overtemp. FI internal
"Internal FI overtemperature"
(interior of FI)
Pos: 645 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ Fehl er E0 02 [ SK 1 80E/SK 2xxE/SK 5xxE/SK2xxE-FDS] @ 2\ mod_1347453302152_388.docx @ 46451 @ @ 1
E002
2.0 Overtemp. Motor PTC
"Overtemperature motor
thermistor "
Motor temperature sensor (PTC) has triggered
Reduce motor load
Increase motor speed
Use external motor fan
2.1 Overtemp. Motor I²t
"Motor overtemperature I²t"
Only if I
2
t motor (P535) is
programmed.
I
2
t motor has triggered (calculated overtemperature of
motor)
Reduce motor load
Increase motor speed
2.2 Overtemp. Brake r.ext
"Overtemperature of external
brake resistor "
Overtemperature via digital
input (P420 […])={13}
Temperature monitor (e.g. brake resistor) has activated
Digital input is Low
Check connection, temperature sensor
Pos: 64 6 /Allg emein/ Allg emeing ültig e Mod ule/---------Sei tenu mbruc h kompakt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1

Table of Contents

Other manuals for Nord Drivesystems NORDAC FLEX SK 225E Series

Related product manuals