NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
244 BU 0200 en-3118
Device type SK 2xxE…
-551-323- -751-323- -112-323-
4 4 4
Nominal motor power
(4-pole standard motor)
±
Input current
Output current
3), 4)
motor mounting
2)
wall mounting
2)
Ω
Ω
Ω
Motor mounting (fan cooling 5), integrated in device)
Max. continuous power / max. continuous current
S1-40°C
5.5kW / 23.0A 7.5kW / 29.0A 11.0kW / 40.0A
Max. permissible ambient temp. with nominal output current
S1
S3 70 % ED 10 min
S6 70 % ED 10 min (100 % / 20 % Mn)
40°C
50°C
40°C
50°C
40°C
44°C
Wall mounting (fan cooling 5), integrated in device)
Max. continuous power / max. continuous current
S1-40°C
5.5kW / 23.0A 7.5kW / 29.0A 11.0kW / 40.0A
Max. permissible ambient temp. with nominal output current
S1
S3 70 % ED 10 min
S6 70 % ED 10 min (100 % / 20 % Mn)
45°C
50°C
45°C
50°C
45°C
47°C
General fuses (AC) (recommended)
UL fuses (AC) – permitted
CC, J, R, T, G, L (300 V)
x 60 A 60 A 60 A
7)
(300 V ) x
60 A 60 A 60 A
1) Note derating curve ( Section 8.4.4 "Reduced output current due to mains voltage").
2) FLA – Full Load Current, maximum current for the entire mains voltage range as stated above (200 V – 240 V) according to UL/CSA
4) SK 21xE and SK 23xE devices: For use of safe functions (functional safety: STO and SS1) the restrictions regarding the permissible temperature
range according to BU 0230 must be noted.
5) Fan cooling, temperature-controlled: ON= 55°C, OFF= 50°C,
After-run time when 50°C limit undershot and enable removed: 2 minutes
6) Maximum permissible mains short circuit current
7) "Inverse time trip type“ according to UL 489