Operating Parameters
B-3
Part 1073401_07
E 2021 Nordson Corporation
3
Change History Log (Noneditable)
Description:
Records the last ten changes made to either the setpoint temperatures or
the operating parameters.
Value:
—
Resolution:
—
Default Value:
P-_ (unused log entry)
Format:
Refer to Section 3, Installation, Review Parameter and Setpoint
Temperature Changes.
Use:
Use the right-display key to review the log entries for the last ten changes
that were made to the operating parameters or the setpoint temperatures.
Empty log entries are indicated by “P-_.”
4 Ready Delay Time
Description:
The amount of time that will elapse after all of the components
have reached their setpoint temperature before the ready LED
will turn on. The ready delay time only functions when the
temperature of the tank, at the time the melter is turned on, is
more than 27 °C (50 °F) from its setpoint temperature. The ready
delay time begins when all components are within 3 °C (5°F) of
their respective setpoint temperature.
Value:
0 to 60 minutes
Resolution:
1 minute
Default Value:
0 minutes
Format:
Left display “rd.” Right display, minutes or seconds remaining.
Use:
The ready delay allows the contents of the tank an additional
amount of time to heat before pump turns on.
NOTE: The time remaining on the ready delay is indicated in
minutes in the right display at the end of every automatic scan
cycle. When the delay time reaches 1 minute, the time
remaining appears in seconds.
5
Service Interval Time
Description:
The number of heater-on hours that must elapse before the service LED
turns on.
Value:
0 hours (disabled) to 8736 (one year)
Resolution:
1 hour
Default Value:
500 hours
Format:
—
Use:
Set the service interval time to signal a user-defined service check or
maintenance event, such as changing the filter. The service LED will turn
on after the pre-set time elapses. With the melter in the scan mode, press
the Clear/Reset key to turn off the service LED and reset the time.