Installation
3-29
Part 1024496_06
2014 Nordson Corporation
Parameter Name Range of Values Default Value
Output Setup
40
Standard Output 1 0–6 1 (Ready)
41
Standard Output 2 0–6 3 (Fault)
42
Standard Output 3 0–6 4
43
Optional Output 4 0–6 0 (disabled)
44
Optional Output 5 0–6 0 (disabled)
45
Optional Output 6 0–6 0 (disabled)
46
Optional Output 7 0–6 0 (disabled)
Seven‐day Clock
50
Current Day 1 to 7 (1 = Monday) —
51
Current hour 0000 to 2359 —
55
Schedule 1 Heaters On 0000 to 2359 06:00
56
Schedule 1 Heaters Off 0000 to 2359 17:00
57
Schedule 1 Enter Standby 0000 to 2359 —:—
58
Schedule 1 Exit Standby 0000 to 2359 —:—
60
Schedule 2 Heaters On 0000 to 2359 —:—
61
Schedule 2 Heaters Off 0000 to 2359 —:—
62
Schedule 2 Enter Standby 0000 to 2359 —:—
63
Schedule 2 Exit Standby 0000 to 2359 —:—
65
Schedule 3 Heaters On 0000 to 2359 —:—
66
Schedule 3 Heaters Off 0000 to 2359 —:—
67
Schedule 3 Enter Standby 0000 to 2359 —:—
68
Schedule 3 Exit Standby 0000 to 2359 —:—
71
Schedule for Monday 0-7 0
72
Schedule for Tuesday 0-7 0
73
Schedule for Wednesday 0-7 0
74
Schedule for Thursday 0-7 0
75
Schedule for Friday 0-7 0
76
Schedule for Saturday 0-7 0
77
Schedule for Sunday 0-7 0