11
Refrigerant Charging Charts For Cooling Mode of Operation
*Note: All pressures are listed in psig. and all temperatures in deg. F.
S4BD-018KA/KB
250
275
300
325
350
375
400
425
450
475
500
525
550
575
600
70 75 80 85 90 95 100 105 110 115 120 125 130
Liquid Temperature (F)
Liquid Pressure (psig)
Remove refrigerant when above the curve
Add refrigerant when below the curve
250
275
300
325
350
375
400
425
450
475
500
525
550
575
600
75 80 85 90 95 100 105 110 115 120 125 130 135
Liquid Temperature (°F)
Liquid Pressure (psig)
Remove
refrigerant
Add
refrigerant
S4BD-024KA/KB
SATURATION