EasyManua.ls Logo

Noritz NRCB180DV - Page 58

Noritz NRCB180DV
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
Setting the Outdoor Reset Control
[0-10 Volt Input control] - [I:01_HCt]
1. Connect Heat Demand (0-10 VDC) to terminal.
(Refer to the figure on the right for details.)
2. The ON/OFF button is OFF.
The Operation Display must be off.
3. Press the SETTING button.
Select using the / buttons,
and then press the ENTER button.
Heat Demand
(0-10 VDC)
* This terminal has
electrical polarity.
[CN235]
0 - 10 V
(
(
)
)
Do NOT connect room thermostat to heat
demand (T-T) when an external control system is
connected.
* The Combi Boiler is activated only by receiving
voltage.
NOTE
DO NOT mix [Room Thermostat
Control], [External Voltage Control
System (without Room Thermostat)]
and [Outdoor Temperature Control
with Outdoor Temperature Sensor
and Room Thermostat]
The ”Installer Mode” screen appears.
4. When entering the “Installer Mode”, display
will change to
1 sec.
, or
1 sec.
.
This function will appear within the first 10
minutes of connecting electrical power and
before pressing the ON/OFF button.
5. When display shows after 1sec.
, press the / buttons to
navigate
1 sec.
in the
“Installer Mode”.
6. Select
1 sec.
, then
press the the ENTER button to enter the
function.
(St: Standard)
7. Press the / buttons to change the
parameter value , and then press
the ENTER button to save the settings and to
exit the function.
The icon will flash if the Heat Demand
Input (0-10 VDC) is not detected.
Connecting Electricity

Table of Contents

Related product manuals