EasyManua.ls Logo

Notifier CHG-120 - Connecting the Charger to a Load; Connecting to Multiple Loads; Wiring Steps for Multiple Loads

Notifier CHG-120
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing the Charger
16
CHG-120 Instruction Manual 11/06/2002 PN 50641:B1
Connecting the Charger to a Load
This section provides two applications for connecting a charger to a load. While connecting
a charger to a load, observe the following precautions:
Make sure all power sources are off to the charger and the load.
Follow polarity when making connections.
Connecting the Charger to a Multiple Load You can connect a charger to multiple
loads, such as a main power supply, auxiliary power supply, amplifiers, and so forth, as
shown in Figure 9.
Figure 9 Typical Wiring for a Charger to a Multiple Load
To connect a charger as shown in Figure 9, follow these steps:
Step Action
1 Cut and remove resistor R104 to disable CHG-120 ground fault protection. Refer to Figure
12 for R104 location.
2 Cut jumper JP1 on the MPS-24A Circuit Board to disable the remote battery charger.
3 Connect the battery+ and battery– terminals of the power supply to the charger output
circuit (TB2: Out 1+ and Out 1–) as shown in Figure 9.
4 Connect the battery+ and battery– terminals of the amplifier to the charger output circuit
(TB2: Out 2+ and Out 2–) as shown in Figure 9.
5 Connect the batteries to the charger (for battery connections see Figure 5 or Figure 6).
CHG-120
AA-30
Amplifier
MPS-24A
Power Supply
Note: Figure 10 shows a
wiring diagram for tying the
load to battery terminals to
obtain additional current.
For example, the first
AA-120 draws 7 A, the
daisy-chained AA-30s draw
7 A, and the second
AA-120 draws 7 A of
additional current from the
batteries.