64 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Remote Terminal Access Using the CRT-2 for Alter Status
C.3.5 Display All Programmed Points
From the “Read Status” menu, select option 3 - Read All Points. The CRT-2 displays a list of the
status of all addressable detectors, modules, system parameters and software zones:
C.3.6 Step-through History
From the “Read Status” menu, select option 4 - History-Step. This option lets you step through all
history events one event at a time. Step through the history list one event at a time by pressing the
Next F5 or Prior F6 function keys.
C.3.7 View All History
From the “Read Status” menu, select option 5 - History ALL. The entire history of events will
display on the screen.
C.3.8 Step-through Alarm History
From the “Read Status” menu, select option 6 - Alarm-History:Step. This option lets you step
through the panel’s alarm history one event at a time by pressing the Next F5 or Prior F6 function
keys.
C.3.9 View All Alarm History
From the “Read Status” menu select option 7 - Alarm History All. This entire history of alarm
events will display on the screen, from most recent to oldest event.
C.4 Using the CRT-2 for Alter Status
C.4.1 Overview
This section shows how to Alter Status functions from a CRT-2.
NORMAL SMOKE(PHOTO) DETECTOR ADDR 1D002 Z003 000%A8 8 ** 1D002
NORMAL SMOKE (ION) DETECTOR ADDR 1D003 Z002 020%A6 6 ** 1D003
NORMAL HEAT(FIXED) DETECTOR ADDR 1D006 Z001 050% * 1D006
NORMAL SMOKE(LASER) DETECTOR ADDR 1D099 Z004 000%A6 6 *V00 1D099
OFF RELEASE CKT MODULE ADDR 1M001 ZR00 I** 1M001
NORMAL MONITOR MODULE ADDR 1M001 ZR00 I** 1M001
OFF RELAY MODULE ADDR 1M033 Z000 *FW 1M033
OFF SOFTWARE ZONE Zone 01 Z01
Press <3> <
ENTER>
************************ ALARM HISTORY START ***********************************
ALARM: MAN_RELEASE MODULE ADDR 1M065 10:21A 011508 1M065
ALARM: MAN_RELEASE MODULE ADDR 1M065 10:19A 011508 1M065
ALARM: MAN_RELEASE MODULE ADDR 1M065 03:20P 011508 1M065
ALARM: SMOKE (ION) DETECTOR ADDR 1D129 03:20P 011508 1M065
Press <7> <
ENTER>
NOTE: The panel must be in Local Terminal Mode (LocT) or Local Monitor Mode (LocM).
NOTE: See the NFS-320 Programming Manual for instructions on enabling the CRT port.