NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 65
Using the CRT-2 for Alter Status Remote Terminal Access
C.4.2 Accessing Alter Status Options
Access Alter Status function from the CRT-2 by following these steps.
1. Turn on the CRT-2 connected to the control panel.
2. Press the Alter Status function key. The control panel displays the Password screen.
3. Enter the Status Change Password. The factory default Status Change Password is 11111.The
password does not display on the CRT-2. Five asterisks will appear in place of the password.
The Alter Status Options menu appears.
From the Alter Status Options menu, you can select 1-5.
C.4.3 Enable or Disable Detectors, Modules or Zones
From the “Alter Status” menu select option 1 - Disable. Disable lets you enable or disable
detectors, modules, or zones.
Enter the following:
1. Enter the first letter to read one of the following, using upper case letters:
2. Detector = D
Module = M
NAC = P
Zone - Z
3. Enter the address or number of the device.
4. Press
ENTER and a display similar to the following will appear.
Function Lets you...
Disable Enable or disable detectors or modules.
Alarm/Pre-Alarm Change the Alarm and Pre-Alarm levels of any addressable detector in the
system.
Clear Verification Clear the verification counter for all the addressable detectors in the system.
Clear History Clear the contents of the History buffer.
Set Action/Alert Set the Pre-Alarm for Alert or Action.
Table C.5 Alter Status Functions
Enter Status CHange Password or Escape to Abort
Press <
ALTER STATUS>
*****
Press <1><1><1><1><1><
ENTER>
1=Disable 2=Alarm/Prealarm 3=Clear Verification 4=Clear History 5=Alert/Action
Disable/Enable. Type D(nnn) / nMnnn / P(nn) / Z(nn) then Enter
STATUS CHANGE Dis/Ena point 8:29A Tue 01/15/08
Press <1><
ENTER>
Number
Address (01-159)

Table of Contents

Other manuals for Notifier NFS-320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-320 and is the answer not in the manual?

Notifier NFS-320 Specifications

General IconGeneral
Operating Temperature32°F to 120°F (0°C to 49°C)
Operating Voltage24 VDC
Humidity10% to 93% non-condensing
SLC Loops1
NAC Outputs2
Power120/240 VAC, 50/60 Hz
CompatibilityNotifier ONYX Series devices
Display80-character LCD
Compatible DevicesNotifier ONYX Series detectors, modules, and notification appliances
Signaling Line Circuits (SLC)1 SLC loop

Related product manuals