64
420012001500 - 03182024 - Rev. 04
Part 9 - Controls
E. Setup wizard
The Setup Wizard allows for the easy
configuration of the following functions:
- AUTO Function (Outdoor Reset) enable/
disable
- Central Heating Zones setup
- DHW setup
- Password Protection enable/disable
- Network (WiFi) Configuration
To start the Setup wizard proceed as follows:
1. From the Main Menu, turn the dial to
highlight “Setup Wizard” and press
ENTER.
2. If prompted, insert the access code;
turn the dial to adjust the value to 234 and
press ENTER.
5. Enable or disabled the AUTO Function
(Outdoor Reset).
Turn the dial to select and press ENTER.
6. Turn the dial to select the number of
CH zones managed by the boiler and
then press ENTER.
7. Select the Type of Heating for the
respective zone. Turn the dial to select:
• High temperature
(e.g Fin-tube Baseboard)
• Medium temperature
(e.g Cast-iron Radiators / Air-handler)
• Low temperature
(e.g Infloor Radiant)
and press ENTER.
8. Review the Max Temperature setting
for the respective zone. Turn the dial to
adjust. Press ENTER to save
9. Review the Min Temperature setting
for the respective zone. Turn the dial to
adjust. Press ENTER to save.
10. If AUTO Function (Outdoor Reset) was
enabled, the controller will prompt you
to input the AUTO Temp Contrl Mode for
each zone. Turn the dial to select:
• Fixed Outlet
• Basic On/Off
• Room Temp
• Outdoor Temp(Factory setting)
• Room&Outdoor
Press ENTER to confirm.
11. DHW Mode (not applicable for Combi
models)
Turn the dial to select:
• Tank Sensor
• Aquastat
• No DHW
Press ENTER.
12. Turn the dial to adjust the DHW setpoint
temperature, and press ENTER to confirm
(not applicable when DHW Mode =
Aquastat)
13. Turn the dial to select Yes or No to enable/
disable Password Protection.
14. Select to activate the Network
conguration. Turn the dial to select Yes
or No and press Enter.
If Yes is selected, follow the instructions on
the display to activate the WiFi connection.
Note: if the boiler is already connected to
WiFi, then select No.
MENU
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
Main Menu
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save
Setup wizard
Boiler Details
User Menu
Tech menu
Test mode
Insert technical code
234
Insert Code
Save
Insert technical code
222
Insert Code
Save
Outdoor rest
AUTO Function
CH - Select the number of heating zone
directly controlled by the boiler
CH
1
Max Temperarture
CH Zone 1
179°F
Min Temperarture
CH Zone 1
104°F
AUTO Temp Contrl Mode
Outdoor Temp
CH Zone 1
Select the type of heating
High Temperature
(e.g Fin-tube Baseboard)
CH Zone 1
Disabled Enabled
Outdoor rest
AUTO Function
Disabled Enabled
Would you like to enable password
protection?
Password Protection
OFF ON
Whould you like to enable password
protection?
Password Protection
OFF ON
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Would you like to connect your
product to the internet?
Network Configuration
NO YES
Whould you like to enable password
protection?
Network Configuration
NO ON
The password is 234
Password Protection
Password Protection deactivated
Password Protection
Save
Tank Sensor
DHW
DHW Mode
Save
DHW
Review DHW setpoint, adjust as desired
Save
Aquastat
Save
Sensor Type
DHW
124°F
Save
Save Save
Save
The display reverts to showing the
previous screen.
Follow the instructions on the display to complete the Network Configuration.
Figure 79 - Setup Wizard process