EasyManua.ls Logo

NTI TRX085 - Page 79

Default Icon
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
79
TRX Series II - Installation - Startup - Maintenance Instructions
Building Management System.
Only visible with 0-10V / 4-20mA Clip-In Board installed
To navigate the BMS Control menu proceed as follows:
1. From the Tech Menu, turn the dial to highlight “BMS Control” and press ENTER.
2. Scroll to the parameter to be adjusted/viewed and press ENTER.
Note: most parameter options will only be visible after setting Control Mode ≠ 0, and after
exiting and reentering the BMS Control menu.
3. Modify the setting by turning the dial, press ENTER to save the value.
Note: pressing ESC exits the screen without saving the new value.
4. Press ESC to return to the previous screen.
Tech Menu
DHW setup
Cascade Setup
Restore/Backup
BMS Control
Complete Menu
BMS Controls
Control mode
Max Temperature
Min Temperature
Control Signal to Start Heat Demand
Control current - start heat Demand
Tech Menu
DHW setup
Cascade Setup
Restore/Backup
BMS Control
Complete Menu
BMS Controls
Control mode
Max Temperature
Min Temperature
Control Signal to Start Heat Demand
Control current - start heat Demand
5. BMS Controls
Figure 96 - Tech Menu
BMS Control
Table 37 - Tech Menu - BMS Controls Menu
Menu Option | Description (Range) Default
CONTROL MODE (42.0.0)
Disabled (0) – the boiler maintains control of the burner power and setpoint
temperature.
0-10V (Power or Temp) (1 or 2) – the boiler power level, or setpoint
temperature, is modulated proportionally to the 0-10V input signal.
Current (Power or Temp) (3 or 4) – the boiler power level, or setpoint
temperature, is modulated proportionally to the 4-20mA input signal.
Disabled
MAX TEMPERATURE (42.0.1)
Sets the maximum boiler temperature, corresponding to an input signal equal to
the Max Control Signal, when Control Mode = 2 or 4. (Range = Min Temperature
to 179°F)
179°F
MIN TEMPERATURE (42.0.2)
Sets the minimum boiler temperature, corresponding to an input signal equal to
the Min Control Signal, when Control Mode = 1 or 3. (Range = 68°F to Max
Temperature)
68°F
CONTROL SIGNAL TO START HEAT DEMAND (42.1.0) / CONTROL CURRENT
– START HEAT DEMAND (42.1.4)
Sets the minimum input control signal required to start a heat demand. (Range =
Control Signal to Stop Heat Demand to Min Control Signal)
1.0V / 4mA
CONTROL SIGNAL TO STOP HEAT DEMAND (42.1.1) / CONTROL CURRENT –
STOP HEAT DEMAND (42.1.5)
Sets the control signal that correlates to the Max Temperature if Control Mode = 2
or 4, or max burner power if Control Mode = 1 or 3. (Range = Min Control Signal
to 10.0V/20mA)
0.5V / 2mA
MAX CONTROL SIGNAL (42.1.2) /CONTROL CURRENT – MAXIMUM DEMAND
(42.1.6)
Sets the control signal that correlates to the Max Temperature if Control Mode =
2 or 4, or max burner power if Control Mode = 1 or 3. (Range = Min Control
Signal to 10.0V/20mA)
10.0V /
20mA
MIN CONTROL SIGNAL (42.1.3) /CONTROL CURRENT – MINIMUM DEMAND
(42.1.7)
Sets the control signal that correlates to the Min Temperature if Control Mode = 2
or 4, or min burner power if Control Mode = 1 or 3. (Range = Control Signal to
Start Heat Demand to Max Control Signal)
2.0V / 4mA
Part 9 - Controls

Other manuals for NTI TRX085

Related product manuals