84
420012001500 - 03182024 - Rev. 04
4. 2. 3 Heating Curve Offset -25 - +25 0
When the Reset Curve results in a boiler target
temperature that is too high or too low (i.e., heats the
building too quickly or slowly), Parallel Shift can be used
to offset the curve up or down to increase or decrease the
boiler target temperature.
NOTE: Adjusting Parallel Shift is only possible when Auto
Boost is OFF (4.7.5 = 0).
4. 2. 4 Room Sensor Influence 0 - 20 4
Adjusts the influence of room temperature on target
boiler temperature - a higher setting causes a greater
increase to the boiler target temperature as the indoor
temperature drops below room setpoint.
Only applicable when using an optional NTI Room
Sensor and when 4.2.1 = 2 or 4.
4. 2. 5 Max Temperature 68 - 179 °F 179
4.2.5 sets the allowable boiler operating temperature
range for Zone 1 heating, limiting Automatic Temperature
Control and manual adjustments from the User Menu.
4. 2. 6 Min Temperature 68 - 1179 °F 95
4.2.6 sets the allowable boiler operating temperature
range for Zone 1 heating, limiting Automatic Temperature
Control and manual adjustments from the User Menu.
4 2. 8 Quick night setback 0 = OFF
1 = ON
0
4 2. 9 Heat request mode 0 = Standard
1 = RT time Programs
Exclusion
2 = Heat demands
forcing
1
4. 3 DIAGNOSTICS
4. 3. 0 Room Temperature Read only
Only applicable when using an NTI room sensor
4. 3. 1 Room Temperature
Setpoint
Read only
Only applicable when using an NTI room sensor
4. 3. 4 Zone 1 Heat Call 0 = OFF
1 = ON (Read only)
4. 3. 8 Zone flow temperature
setpoint
Read only
4. 7 ZONE REGULATION PARAMETERS
4. 7. 5 Auto Slope Boost 0 = OFF
1 = ON
0
See L. Auto Boost.
5 ZONE 2 PARAMETERS
5. 0 TEMPERATURE SETTINGS
5. 0. 0 Room Setpoint
(Comfort)
50 - 86 °F 66
Only applicable when using an NTI room sensor
5. 0. 1 Room Setpoint
(Reduced)
32 - 86 °F 61
Only applicable when using an NTI room sensor
5. 0. 2 Zone 2 Fixed Water
Temp
68 - 179 °F 179
5. 0. 3 Room Setpoint (Holiday/
Anti-frost)
36 - 75 °F 41
Only applicable when using an NTI room sensor
Changes all zones
5. 0. 5 CH Target temperature
logic
0 = Max active zone
target
1= Z1,Z2,Z3....etc.
2= Min active zone
taget
1
5. 1 AUTOMATIC WINTER MODE
5. 1. 0 Warm weather
shutdown
0 = OFF
1 = ON
0
5. 1. 1 WWSD threshold 50 - 86 °F 68
5. 1. 2 WWSD Switchoff delay 0 - 300 minutes 2
5. 2 ZONE 2 SETTINGS
5. 2. 1 Auto Temperature
control mode
0 = Fixed Outlet
1 =Basic On/Off
2 =Room Temp
3 =Outdoor Temp
4 =Room&Outdoor
3
5. 2. 2 Heating Curve Slope 0.2 - 3.5 1.3
See graph and description of Parameter 422.
5. 2. 3 Heating Curve Offset -25 - +25 0
See description of Parameter 4.2.3
5. 2. 4 Room Sensor Influence 0 - 20 4
Adjusts the influence of room temperature on target
boiler temperature - a higher setting causes a greater
increase to the boiler target temperature as the indoor
temperature drops below room setpoint.
Only applicable when using an optional NTI Room
Sensor and when 5.2.1 = 2 or 4.
5. 2. 5 Max Temperature 68 - 179 °F 179
5.2.5 sets the allowable boiler operating temperature
range for Zone 2 heating, limiting Automatic Temperature
Control and manual adjustments from the User Menu.
5. 2. 6 Min Temperature 68 - 179 °F 95
5.2.6 sets the allowable boiler operating temperature
range for Zone 2 heating, limiting Automatic Temperature
Control and manual adjustments from the User Menu.
5. 2. 8 Quick night setback 0 = OFF
1 = ON
0
5. 2. 9 Heat request mode 0 = Standard
1 = RT time Programs
Exclusion
2 = Heat demands
forcing
1
5. 3 DIAGNOSTICS
5. 3. 0 Room Temperature Read only
Only applicable when using an NTI room sensor
5. 3. 1 Room Temperature
setpoint
Read only
Only applicable when using an NTI room sensor
5. 3. 4 Zone 2 Heat Call 0 = OFF
1 = ON (Read only)
5. 3. 8 Zone flow temperature
setpoint
Read only
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
Note
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
Note
Part 9 - Controls