Table 4.7 Other Alarms Configuration Sub-Menu
O LOAD = {ENA or DIS}
O LOAD = {0.3 to 100.0} A
O LOAD FILTER = {0 to 12} S
I LOAD = {ENA or DIS}
I LOAD = {0.3 to 100.0} A
I LOAD FILTER = {0 TO 12} S
I GFI = {ENA or DIS}
I GFI = {20 to 250} mA
I GFI FILT ER = {0 to 12} S
FI TRIP = {ENA or DIS}
FI TRIP = {20 to 250} mA
O VOLT = {ENA or DIS}
O VOLT = {10 to 330} V
O VOLT FILTER = {0 to 12} S
I VOLT = {ENA or DIS}
I VOLT = {10 to 330} V
I VOLT FILTER = {0 to 12} S
O RESIST = {ENA or DIS}
O RESIST = {1 to 100} %
O RESIST FILTER = {0 to 12} S
I RESIST = {ENA or DIS}
I RESIST = {1 To 250} %
I RESIST FILTER = {0 to 12) S
OMINAL RESIST = {2.00 to 2000.00} Ω (only if LO or HI is enabled)
VERCURRENT TRIP = {ENA or DIS} (only if SSR is being used)
WITCH FAIL = {ENA or DIS}
TC RESET = {ENA or DIS}
.B. LIMITING = {ENA or DIS} (only if SSR is being used)
OWER LIMITING = {ENA or DIS} (only if SSR is being used)
WITCH LIMITING = {ENA or DIS} (only if SSR is being used)
ONTACTOR COUNT = {ENA or DIS} (only if Deadband or Prop Amb
Contactor are being used)
ONTACTOR COUNT = {0 to 999999} (only if Deadband or Prop Amb
Contactor are being used)
EEROM DATA FAIL = {ENA or DIS}
---- END ----
ONTROL SETPOINT = 20°C
O TS 1 = –10°C
O LOAD = 1.0 A
I GFI = 50 mA
FI TRIP = 75 mA
S ALARMS CONFIG…
THER ALARMS CONFIG…
OINT SETUP…
ISC SETUP…
OMMUNICATIONS SETUP…
---- END ----