nVent.com | 23
4.3.5 “POINT SETUP…” SUB-MENU
The “Point Setup” sub-menu is used to configure parameters that relate directly to the specific
control point. Included in this menu are control mode settings, circuit breaker and switch
ratings, autocycle set-up parameters, etc.
4.3.5 “POINT SETUP…” SUB-MENU
The “Point Setup” sub-menu is used to configure parameters that relate directly to the specific
control point. Included in this menu are control mode settings, circuit breaker and switch
ratings, autocycle set-up parameters, etc.
Table 4.8 Point Setup Sub-Menu
AG = {19 ALPHANUMERIC CHARACTERS}
WITCH CONTROL MODE = {PROPORTIONAL, PROP AMB SSR, DEADBAND, or
PROP AMB CONTACTOR}
EADBAND = {1 to 50}°C (only if SWITCH CONTROL MODE
is DEADBAND)
ROP BAND = {1 to 50}°C (only if SWITCH CONTROL MODE
is not DEADBAND)
YCLE TIME = {10 to 255} MIN (only if SWITCH CONTROL MODE
is not PROP AMB CONTACTOR)
WITCH RATING = {0.3 to 100.0} A (only if SSR is being used)
IRCUIT BREAKER = {0.3 to 100.00} A (only if SSR is being used)
AX POWER = {3 W to 33,000} W ( only if SSR is being used)
S FAIL MODE = {OFF or ON}
S CTL MODE = {TS 1-FAIL OFF (ON) or
TS 1-FAIL TO TS 2 or
TS 2-FAIL OFF (ON) or
TS 2-FAIL TO TS 1 or
AVERAGE-FAIL OFF (ON) or
AVERAGE-FAIL TO GOOD or
LOWEST-FAIL OFF (ON) or
LOWEST-FAIL TO GOOD}
S 1 TYPE = {100 W PLAT or NI-FE}
S 1 LEAD RESIST = {1 to 20.000} Ω (only if TS 1 TYPE = NI-FE)
S 1 HI LIMIT = {ENA or DIS}
S 2 TYPE = {100 W PLAT or NI-FE}
S 2 LEAD RESIST = {0 TO 20.000} Ω (only if TS 2 TYPE = NI-FE)
S 2 HI LIMIT = {ENA or DIS}
UTO-CYCLE = {ENA or DIS}
UTO-CYCLE INTERVAL = {1 to 240} (only if AUTO-CYCLE=ENA)
UTO-CYCLE UNITS = {HOURS or MINUTES} (only if AUTO-CYCLE=ENA)
VERRIDE SOURCE = {REMOTE or EXT INPUT}
OAD SHEDDING = {ENA or DIS}
---- END ----
ONTROL SETPOINT = 20°C
O TS 1 = –10°C
O LOAD = 1.0 A
I GFI = 50 mA
FI TRIP = 75 mA
S ALARMS CONFIG…
THER ALARMS CONFIG…
OINT SETUP…
MISC SETUP…
OMMUNICATIONS SETUP…
---- END ----