Performance Specifications & Requirements
9
Do not install e-Series heat pumps such that they would need to be operated in conditions
outside of these performance specifications. Units may stop compressor operation outside
of ambient temperature limits. In cold climates, freeze protection measures will remain active
when the compressor is turned o.
Table 2: Electrical Specifications
Standard Power Package Unied Power Package
Model: e360-230v e360-460v e360-230v e360-460v
Main 3-Phase Power Feed: 208-230/3/60 460/3/60 208-230/3/60 460/3/60 Volt/Phase/Hz
Min. Circuit Ampacity (MCA) 123 63 129 66 Amps
Max. Overcurrent Protecon (MOCP) 222 113 228 116 Amps
Running Load Amps (RLA) 110 57 110 57 Amps
Power Factor 0.86 0.86
Short Circuit Current Rang (SCCR) 100 100 kA
Internal Component Data:
Fan Motor Full Load Amps (FLA) 10.1 6 10.1 6 Amps
Fan Horsepower (HP) 5.1 6.02 5.1 6.02 HP
Compressor Locked Rotor Amps (LRA) 294 245 294 245 Amps
Internal Pump Full Load Amps (FLA) On Backup Feed 2.1 Amps
Compressor Horsepower (HP) 30 30
Backup Circuit Single Phase Power Feed: 120/1/60 Volt/Phase/Hz
Min. Circuit Ampacity (MCA) 14 14 Amps
Full Load Amps (FLA) 11.3 11.1 Amps
Max. Overcurrent Protecon (MOCP) 25 20 Amps
Internal Pump Full Load Amps (FLA) 2.1 2.1 Amps
Circuit Power 1360 1330 Was
Short Circuit Current Rang (SCCR) 100 kA