Expanded Performance Data
10
Expanded Performance Data: 140 Leaving Water Temp.
e360 Performance Data: 70 Deg F. Entering Water
Ambient Heating Cap. Cooling Cap. Heat COP Cool COP Flow
10 Deg. F. 98 kBTU/hr 68 kBTU/hr 2.6 1.8 4.2 GPM
24 Deg. F. 126 kBTU/hr 93 kBTU/hr 2.9 2.1 5.5 GPM
30 Deg. F. 141 kBTU/hr 107 kBTU/hr 3.0 2.3 6.2 GPM
40 Deg. F. 171 kBTU/hr 133 kBTU/hr 3.3 2.6 7.4 GPM
50 Deg. F. 205 kBTU/hr 165 kBTU/hr 3.8 3.1 9.3 GPM
60 Deg. F. 241 kBTU/hr 202 kBTU/hr 3.9 3.3 10.5 GPM
70 Deg. F. 287 kBTU/hr 242 kBTU/hr 4.1 3.5 12.3 GPM
80 Deg. F. 333 kBTU/hr 282 kBTU/hr 4.4 3.7 14.0 GPM
90 Deg. F. 351 kBTU/hr 327 kBTU/hr 4.9 4.6 15.9 GPM