HeatWater.com | WaterService@nyle.com | (800) 777-6953 | Rev. IM-E360-060523 HeatWater.com | WaterService@nyle.com | (800) 777-6953 | Rev. IM-E360-060523
General Description
6
Purpose:
e-Series units are air-to-water Commercial Heat Pump Water Heaters
(CHPWHs) using R-513a refrigerant in a closed and factory charged circuit. A
double wall heat exchanger provides heat to a potable water circuit. Potable
water is piped to the heat pump in a loop to and from external storage tanks.
Circulation is provided by the integral circulator in the heat pump.
Usage:
the e-series of water heaters are designed to provide hot water in a “Single
Pass” configuration; meaning that water is delivered at full usable temperature
to the potable storage tank in one pass. This allows for faster recovery of usable
water temperatures than in traditional “Multi-Pass” configurations. This system
is not an “on demand” heater and does require external and stratified storage to
operate eectively. Building recirculation loops must be returned to a separate
“swing tank” to preserve this stratification.
Ease of Installation:
The enclosure is designed to minimize its footprint, and to simplify placement
considerations for multiple-unit installations. As a “monobloc” style heat pump,
the unit arrives ready to connect to electrical, condensate, optional ducting, and
potable water infrastructure in the field.
It features onboard defrost heaters and heat tracing for cold climate usage, an
integral circulator and control valve, and an internal condensate drain pan with
a pipe connection point. The system is coated to resist salt spray corrosion for
coastal environments. While typically installed outdoors, interior locations with
adequate and consistent ventilation or heat gain can also house the unit, such
as large server rooms or parking garages. e-Series heat pumps can also be
fully ducted, allowing installation indoors in rooms that would not otherwise be
suitable for the heat pump.
General Description