Routine Maintenance
57
Annual Checks:
Note: for checks “during operation”, wait for at least 20 minutes after startup before
confirming relevant data points.
Confirm flow rate using the “Max Pump” button on the control interface,
and verify that flow is at or above maximum design flow for the unit.
Descale heat exchanger if necessary (low flow unsolved by purging/
pipe/pump inspection).
Operate all relief valves and inspect for signs of weepage or leaking.
Ducted Systems: confirm airflow through the evaporator using the “max
fan” button on the control interface, and taking static pressure readings as
described in the startup procedure checklist section of this manual.