US-ENGLISH
US-ENG- 10
2.4.5 - Positioning of the unit on the mounting brackets
Usingthetwopreviouslydrilledholes(seeg.6),securethemountingbracket(L)tothewallusingthesup-
pliedwallarchoringscrews(H)(g.24).Checktoensurethemountingbracketisrmlyanchoredtothewall.
Proceed as follows:
a. After checking thatthexingbracketiswellanchoredtothewall(g.25).
b. Raisetheunitholdingitbythesidesofthelowerbaseandhangitonthebrackets(g.26,ref.L).Slightly
tilt the lower part of the unit towards yourself to make it easier to hang the unit on the brackets.
c. To make the electrical connection and fasten the condensate drain tube, place a wedge between the
unitandthewall(seeg.27).
d. Whennished,carefulllyinspecttoensuretherearenogapsatthebackoftheunit.Theinsulatinggasket
musttrmlyagainstthewall,particularlyintheareawherecondenserairentersandleavestheunit.
2.4.6 - Electric connection
Theunitisttedwithapowercordwithaplug.Ifthewallsocketis
within the length of the cord simply plug it in.
Before connecting the unit, ensure that:
• The power supply voltage and frequency values comply with those indicated
on the data plate of the unit.
• The power supply line is tted with an ecient earth connection that is ap-
propriately sized for the maximum absorption of the conditioner (minimum
cross-section of the cable must be 14 AWG).
• The appliance is powered exclusively through a socket that is compatible with
the plug supplied.
Any replacement of the power cable must be carried out solely by authorized
technical support or by similarly qualied personnel.
On the power supply line of the appliance there must be an adequate omnipolar
disconnection device that complies with the national installation regulations.
It is, however, necessary to check that the electrical power supply is equipped
with ecient earthing and with adequate protections against overloading and/
or short circuits (a 15 amp AT delayed fuse or other devices with equivalent
functions are recommended).
It is possible to proceed with the electrical connection using a cable embedded into the wall in a position as
indicated in the installation template (recommended connection for installing the unit is to the upper part of
the wall).
• This operation must be performed only by the installer or any similarly qualied
personnel and in compliance with local, state and/or national regulations.
• To prevent the risk of an electric shock it is mandatory to switch o the main
switch before performing the electrical connections or any maintenance op-
eration to the appliances.