Section 5 - Specifications
5.1 - General
Temperature Range -18 to 538°C (0 to 1000°F)
Accuracy @ 22°C (72°F) ± 2% of Rdg. or 2.2°C (4°F) whichever is
ambient temperature & greater
emissivity of 0.95 or greater
Optical Field of View 6:1 (Distance/Spot Size)
Repeatability ± 1% of Rdg.
Spectral Response 5 to 14 microns
Response Time 150 msec (0 to 63% of final value)
Emissivity Range 0.1 to 0.99, adjustable
Operating Ambient Temperature
Main Transmitter 0 to 50°C (32 to 122°F)
Sensor Head 0 to 70°C (32 to 158°F)
Sensor Head (-HT Model) 0 to 85°C (32 to 185°F)
Sensor Head with OS100-WC
(Water Cooling Jacket) 0 to 200°C (32 to 392°F)
Operating Relative Humidity Less than 95% RH, non-condensing
Water Flow Rate for OS100-WC 0.25 GPM, room temperature
Thermal Shock About 30 minutes for 25°C
abrupt ambient temperature change
Warm Up Period 3 minutes
Air Flow Rate for OS100-AP 1 CFM (0.5 Liters/sec.)
Power 12 to 24 VDC @ 100 mA
Analog Outputs
MV-F 1 mV/°F
MV-C 1 mV/°C
K K Type TC - OS101 only
MA 4 to 20 mA
V1 0 to 5 VDC
Output Load requirements
Min. Load (0 to 5VDC) 1 K-Ohms
Max. Load (4 to 20 mA) (Supply Power - 4 )/20 mA
Transmitter Housing NEMA-4 & IP65, Die Cast Aluminum
Sensor Head Housing NEMA-4 , Aluminum
Alarm Output Open Drain, 100 mA
Alarm Set Point 0 to 100% , Adjustable via P4
Alarm Deadband 14°C (25°F)
OS100 Series - Specifications
5
5-1