Section 6. System Programming
6-19
Bell/Siren Supervision
Select this option to comply with NFPA 72 requirements. If selected, the
bell/siren will be supervised for an open circuit across the alarm sounder output terminals. If a fault is
detected, the keypad will display a bell supervision condition.
Q 12, L4
Enter the digit for the desired options from the table below.
Test Interval by Time
L4
Entry Disable Every Hour 1 Day 7 Days 27 Days 60 Days 90 Days 180 Days
0
1
2
3
4
5
6
7
Test Interval Reset by Event
9
A
B
C
D
E
Test Interval by Time:
Test reports will be sent at the time interval selected. The time of day that the
report is sent is defined in Question 22, Locations 14.
Test Interval Reset by Event:
Test reports will be sent at the time interval selected unless an event
that caused a dialer report occurred before the time interval expired. In this case, no test report is sent.
This cuts down the communication traffic to the central station.
QUESTION 13 OTHER SYSTEM OPTIONS
L1 L2 L3 L4
This question defines other system options. Enter the digits as follows: