INSTALLATION
2.3 Installation environment
•
Increased ambient temperature will shorten the life of the inverter.
• Keep the inverter away from heating elements (such as a braking resistor, DC reactor, etc.). If the inverter is installed in a con-
trol panel, keep the ambient temperature within the range of the specifications, taking dimensions and ventilation into con-
sideration.
• You can install multiple 3G3JX inverters side by side in the control panel (side-by-side installation). Again, keep the ambient
temperature within the specified range (40°C or below).
• If the ambient temperature is from 40°C through to 50°C, the carrier frequency should be reduced and the inverter capacity
should be increased.
Airflow
Wall
10 cm min.
5 cm min. 5 cm min.
10 cm min.