32 JX Quick Start Guide
PARAME TER LIST
4.5 Parameter group H
4.6 Parameter group F
C074 Communication parity selection 00: No parity
01: Even
02: Odd
00 No – 113B
C075 Communication stop bit selection 1: 1-bit
2: 2-bit
1 No – 113C
C076 Communication error selection 00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free run
04: Deceleration Stop
02 No – 113D
C077 Communication error timeout 0.00 to 99.99 0.00 No s 113E
C078 Communication wait time 0. to 1000. 0. No ms 113F
C081 O adjustment 0.0 to 200.0 100.0 Yes % 1141
C082 OI adjustment 1142
C086 AM offset adjustment 0.0 to 10.0 0.0 Yes V 1145
C091 Not used Use “00” (Do not change) 00 – – –
C101 UP/DWN selection 00: Do not store the frequency data
01: Store the frequency data
00 No – 1149
C102 Reset selection 00: Trip reset at rising edge of RS input
01: Trip reset at falling edge of RS input
02: Enabled only during trip (Reset at rising edge of RS
input)
00 No – 114A
C141 Logic operation function A input 00: RUN (signal during RUN)
01: FA1 (constant speed arrival signal)
02: FA2 (over set frequency arrival signal)
03: OL (overload warning)
04: OD (excessive PID deviation)
05: AL (alarm output)
06: Dc (disconnection detected)
07: FBV (PID FB status output)
08: NDc (network error)
10: ODc (do not use)
43: LOC (light load detection signal)
00 No – 1150
C142 Logic operation function B input 01 1151
C143 Logic operator selection 00: AND
01: OR
02: XOR
00 No – 1152
C144 Output terminal 11 ON delay 0.0 to 100.0 0.0 No s 1153
C145 Output terminal 11 OFF delay 1154
C148 Relay output ON delay 0.0 to 100.0 0.0 No s 1157
C149 Relay output OFF delay 1158
Parameter
No.
Function name Monitoring or data range (digital operator)
Default
setting
Changes
during
operation
Unit
Modbus
address
(hex)
H003 Motor capacity selection 200-V class: 0.2/0.4/0.75/1.5/2.2/3.7/5.5/7.5
400-V class: 0.4/0.75/1.5/2.2/3.7/5.5/7.5
Factory
default
No kW 1165
H203 2nd motor capacity selection 1541
H004 Motor pole number selection 2/4/6/8 4 No Pole 1166
H204 2nd motor pole number selection 1542
H006 Stabilization parameter 0. to 255. 100 Yes % 1168
H206 2nd stabilization parameter 1544
Parameter
No.
Function name Monitoring or data range (digital operator)
Default
setting
Changes
during
operation
Unit
Modbus
address
(hex)
F001 Output frequency setting/monitor Starting frequency to 1st or 2nd max. frequency – Yes Hz –
F002 Acceleration time 1 0.01 to 3000. 10.0 Yes s 1014 (high)
1015 (low)
F202 2nd acceleration time 1 1501 (high)
1502 (low)
F003 Deceleration time 1 0.01 to 3000. 10.0 Yes s 1016 (high)
1017 (low)
F203 2nd deceleration time 1 1503 (high)
1504 (low)
F004 Operator rotation direction selection 00: Forward
01: Reverse
00 No – 1018
Parameter
No.
Function name Monitoring or data range (digital operator)
Default
setting
Changes
during
operation
Unit
Modbus
address
(hex)