JX Quick Start Guide 5
INSTALLATION
2 INSTALLATION
2.1 Wiring sizes and protection
2.2 Installation dimensions
Motor output (kW) Inverter model 3G3JX-
Wi rin g Applicable device
Power cable (mm
2
)
Earth leakage breaker (ELB) Fuse size (class J) Rated 600 V
0.2 A2002 1.25 5 A 10 A
0.4
A2004
1.25 5 A
10 A
A4004 3 A
0.75
A2007 2.0 10 A 15 A
A4007 1.25 5 A 6 A
1.5
A2015 2.0 15 A 15 A
A4015 2.0 10 A 10 A
2.2
A2022 2.0 20 A 20 A
A4022 2.0 10 A 10 A
3.7
A2037 3.5 30 A 30 A
A4040 2.0 15 A 15 A
5.5
A2055 5.5 50 A 40 A
A4055 3.5 30 A 20 A
7.5
A2075 8.0 60 A 50 A
A4075 3.5 30 A 25 A
0.2 AB002 2.0 5 A 14 A
0.4 AB004 2.0 5 A 
0.75 AB007 2.0 10 A 
1.5 AB015 5.5 15 A 
2.2 AB022 5.5 20 A 
Vol tag e class
Max. applicable
motor output kW
Inverter model 3G3JX- Figure
Dimensions in mm
W1 H1 W H D t1 D1 Weight ( kg)
Single-phase
200 V
0.2 AB002
1 67 143 80 155
95.5
2.6
13 0.8
0.4 AB004 109.5 27 0.9
0.75 AB007
2 98 176 110 189
130.5 28 1.5
1.5 AB015
157.5 6 55
2.3
2.2 AB022 2.4
Three-phase
200 V
0.2 A2002
1 67 143 80 155
95.5
2.6
13 0.8
0.4 A2004 109.5 27 0.9
0.75 A2007 132.5 50 1.1
1.5 A2015
2
98 176 110 189 157.5 6 55
2.2
2.2 A2022
2.4
3.7 A2037
5.5 A2055
164 235 180 250 167.5 1.6 77.5 4.2
7.5 A2075
Figure 1
Figure 2
6
5
5
W
H1
W1
H
t1
D1
1.9
D
H1
5
H
W1
W
5
6
t1
D1
D
1.9

Other manuals for Omron 3G3JX