274
converted back to the range 0000 to 1770 Hex, again using APR(069), for output
from the Analog Output Unit.
ARP
From Analog Input Unit
Analog input word
Control Data
C (DM 1000): C000 Hex (binary with one table)
C+1 (DM 1001): 1770 Hex (Xm)
C+2 (DM 1002): 0000 Hex (Yo)
C+3 (DM 1003): 1770 Hex (X1)
C+4 (DM 1004): FFFF Hex (Y1)
Control Data
C (DM 1500): 0000 Hex (binary with one table)
C+1 (DM 1501): FFFF Hex (Xm)
C+2 (DM 1502): 0000 Hex (Yo)
C+3 (DM 1503): FFFF Hex (X1)
C+4 (DM 1504): 1770 Hex (Y1)
Control Data
C+6 (DM 2506):
88
Valid number of bits: 16 (0000 to FFFF Hex)
Valid number of bits: 16 (0000 to FFFF Hex)
To Analog Output Unit
Execution
condition
PID
ARP
DM 1000
DM 2000
DM 2000
DM 2500
DM 3000
DM 3000
Analog output word
DM 1500
0000 X1: 1770
(x m)
X
(Hex)
Y1: FFFF
0000 X1: FFFF
(x m)
Y1: 1770
Y (Hex)
Y0: 0000
Y (Hex)
Y0: 0000 X
(Hex)
Special Math Instructions Section 5-21