EasyManua.ls Logo

Omron C200HX - Page 50

Omron C200HX
586 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Group-2 High-density I/O Units and B7A Interface Units are allocated words be-
tween IR 030 and IR 049 according to I/O number settings made on them and do
not use the words allocated to the slots in which they are mounted. For 32-point
Units, each Unit is allocated two words; for 64-point Units, each Unit is allocated
four words. The words allocated for each I/O number are in the following tables.
Any words or parts of words not used for I/O can be used as work words or bits in
programming.
32-point Units 64-point Units
I/O number
Words I/O number Words
0 IR 30 to IR 31 0 IR 30 to IR 33
1 IR 32 to IR 33 1 IR 32 to IR 35
2 IR 34 to IR 35 2 IR 34 to IR 37
3 IR 36 to IR 37 3 IR 36 to IR 39
4 IR 38 to IR 39 4 IR 38 to IR 41
5 IR 40 to IR 41 5 IR 40 to IR 43
6 IR 42 to IR 43 6 IR 42 to IR 45
7 IR 44 to IR 45 7 IR 44 to IR 47
8 IR 46 to IR 47 8 IR 46 to IR 49
9 IR 48 to IR 49 9 Cannot be used.
A IR 330 to IR 331 A IR 330 to IR 333
B IR 332 to IR 333 B IR 332 to IR 335
C IR 334 to IR 335 C IR 334 to IR 337
D IR 336 to IR 337 D IR 336 to IR 339
E IR 338 to IR 339 E IR 338 to IR 341
F IR 340 to IR 341 F Cannot be used.
Note Unit numbers A to F cannot be set when using the following CPU Units:
C200HE-CPU32(-Z), C200HE-CPU42(-Z), C200HG-CPU33(-Z), C200HG-
CPU43(-Z), C200HX-CPU34(-Z), and C200HX-CPU44(-Z). Set unit number 0
to 9 when using these CPU Units.
When setting I/O numbers on the High-density I/O Units and B7A Interface
Units, be sure that the settings will not cause the same words to be allocated to
more than one Unit. For example, if I/O number 0 is allocated to a 64-point Unit,
I/O number 1 cannot be used for any Unit in the system.
Group-2 High-density I/O Units and B7A Interface Units are not considered Spe-
cial I/O Units and do not affect the limit to the number of Special I/O Units allowed
in the System, regardless of the number used.
The words allocated to Group-2 High-density I/O Units correspond to the con-
nectors on the Units as shown in the following table.
Unit Word Connector/row
32-point Units
m Row A
p
m + 1 Row B
64-point Units
m CN1, row A
p
m + 1 CN1, row B
m + 2 CN2, row A
m + 3 CN2, row B
Note 1. Group-2 High-density I/O Units and B7A Interface Units cannot be mounted
to Slave Racks.
2. Refer to the Installation Guide for limitations on the number of Special I/O
Units that can be mounted to Slave Racks.
Allocation for Group-2
High-density I/O Units and
B7 Interface Units
See
note.
IR (Internal Relay) Area Section 3-3

Table of Contents

Related product manuals