Section 1: Introduction
This document explains the theory, operation & setup of the Omron CP1W-ETN01-US
Ethernet to Serial adapter.
The CP1W-ETN01-US is an Ethernet to Serial adapter that allows FINS Ethernet
devices to communicate with CP1H and CP1L PLCs. These devices include PCs with
CX-Programmer, NS series HMI products, and software packages that use Omron FINS
Gateway or Sysmac Gateway communications drivers. The adapter mounts in the
Option Board Slot on the front of a CP1H or CP1L PLC, and can be used in all CP1H /
CP1L PLCs with an available Option Board Slot.
Because the adapter is an Ethernet to Serial adapter, it will behave with the response
characteristics of a serial port, and with throughput and frame length limits associated
with serial communications protocols.
The CP1W-ETN01-US adapter converts incoming Omron FINS Ethernet commands to
CV Mode Hostlink commands, and delivers the commands to the PLC CPU. The
adapter then converts the CV Mode Hostlink response from the PLC CPU back to a
FINS Ethernet packet, and delivers it to the originating device (PC or HMI). This
conversion process can be used with either FINS UDP or FINS TCP, using UDP or TCP
port 9600.
If you will be using CX-Programmer to communicate to the adapter, you must have
CX-Programmer Version 8.0 or later installed. CX-One Version 3 includes CX-
Programmer 8.0.
Page 2 of 8

Other manuals for Omron CP1L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CP1L and is the answer not in the manual?

Omron CP1L Specifications

General IconGeneral
ModelCP1L
Data Memory Capacity32K words
Program Capacity10K steps
Communication PortsUSB, RS-232C
ExpansionI/O
Pulse Output100 kHz
Built-in I/ODigital I/O
Expansion SlotsSupports up to 3 expansion units
Operating Voltage100-240 VAC or 24 VDC (varies by model)
Operating Temperature55 degrees Celsius
Storage Temperature75 degrees Celsius
Vibration Resistance10 to 57 Hz, 0.075 mm amplitude
Shock Resistance147 m/s^2, 3 times in X, Y, and Z directions