I/O Memory Allocation Section 9-3
205
Address CS/CJ-series PLC CX-Simulator
Words Bits
Name
Function Settings Function Settings
A29508 Instruction
Processing
Error Flag
This flag and the Error Flag (ER)
will be turned ON when an in-
struction processing error has
occurred and the PLC Setup has
been set to stop operation for an
instruction error. CPU Unit op-
eration will stop and the
ERR/ALM indicator will light
when this flag goes ON.
(The task number where the
error occurred will be stored in
A294 and the program address
will be stored in A298 and A299.)
1: Error
Flag
ON
0: Error
Flag
OFF
Same as
CS/CJ-series
PLC.
A295
A29509 Indirect
DM/EM
BCD Error
Flag
This flag and the Access Error
Flag (AER) will be turned ON
when an indirect DM/EM BCD
error has occurred and the PLC
Setup has been set to stop op-
eration an indirect DM/EM BCD
error. (This error occurs when
the content of an indirectly ad-
dressed DM or EM word is not
BCD although BCD mode has
been selected.) CPU Unit opera-
tion will stop and the ERR/ ALM
indicator will light when this flag
goes ON.
(The task number where the
error occurred will be stored in
A294 and the program address
will be stored in A298 and A299.)
1: Not BCD
0: Normal
Same as
CS/CJ-series
PLC.
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr

Table of Contents

Other manuals for Omron CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CS Series and is the answer not in the manual?

Omron CS Series Specifications

General IconGeneral
BrandOmron
ModelCS Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals