Enclosed Switch D4C F-15
Limit
Switches
Ratings for Pre-wired Models
Note 1. Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
2. Lamp loads have an inrush current of 10 times the steady-state current.
3. Motor loads have an inrush current of 6 times the steady-state current.
UL/CSA Approved Ratings
B300 (D4C-16@@, -17@@), B150 (D4C-26@@, -27@@)
NEMA B300 (D4C-16@@, -17@@) NEMA B150 (D4C-26@@, -27@@)
TÜV Rheinland Approved Ratings (EN60947-5-1)
Applicable Load Range
Rated
voltage
Non-inductive load Inductive load Inrush current
Resistive load Lamp load Inductive load Motor load
NC NO NC NO NC NO NC NO NC NO
125 VAC 1 1 1 0.7 1 1 1 1 20 A max. 10 A max.
30 VDC11111111
Rated
voltage
Carry
current
Current Volt-amperes
Make Break Make Break
120 VAC 5 A 30 A 3 A 3,600 VA 360 VA
240 VAC 15 A 1.5 A
Rated
voltage
Carry
current
Current Volt-amperes
Make Break Make Break
120 VAC 5 A 30 A 3 A 3,600 VA 360 VA
Model Category and rating I the
D4C-1@@@ AC-15 2 A/250 VAC
DC-12 2 A/30 VDC
5 A
4 A
D4C-2@@@ AC-15 2 A/125 VAC 5 A
D4C-3@@@ DC-12 2 A/30 VDC 4 A
D4C-4@@@ AC-14 0.1 A/125 VAC
DC-12 0.1 A/30 VDC
0.5 A
0.5 A
D4C-5@@@ AC-14 0.1 A/125 VAC 0.5 A
D4C-6@@@ DC-12 0.1 A/30 VDC 0.5 A
D4C-6@@@
D4C-5@@@
D4C-4@@@
5 mW 0.8 W
Current I (mA)
D4C-1@@@
D4C-2@@@
D4C-3@@@
Voltage (VDC)