6-8 Advanced Function Setting Level
6
This parameter enables or disables the LBA function and sets the detection time interval.
lba
LBA Detection Time
A Standard Model must be used.
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
• To disable the LBA function, set 0.
Related Parameters
Alarm 1 to 4 Type (Initial Setting Level): Page 6-48
LBA Level (Advanced Function Setting Level): Page 6-79
LBA Band (Advanced Function Setting Level): Page 6-80
lbal
LBA Level
A Standard Model must be used.
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
The LBA detection time must not be 0.
• This parameter sets the LBA level.
• If the deviation between the SP and PV exceeds the LBA level, a loop burnout is
detected.
Related Parameters
Process Value/Set Point (Operation Level): Page 6-8
Alarm 1 to 4 Type (Initial Setting Level): Page 6-48
LBA Detection Time (Advanced Function Setting Level): Page 6-79
LBA Band (Advanced Function Setting Level): Page 6-80
Setting range Unit Default
0 to 9999 Seconds 0
Setting range Unit Default
Temperature input 0.1 to 999.9 °C or °F8.0
Analog input 0.01 to 99.99 %FS 10.00