EasyManuals Logo

Omron E5CC-T Communications Manual

Omron E5CC-T
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
6 Programless Communications
6 - 44
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
(2) We will change the communications settings for CH1.
Change the following settings, and then click the OK Button. Use the defaults settings for
the other parameters.
Parity Bit: Exist
Even/odd parity: Even
Stop bit: 2
Sum check code: Exist
Online Change: Enable
Setting modifications: Enable
Communication rate setting: 57600 bps (This setting can be changed after you change
the communication protocol setting.)
Communication protocol setting: MC protocol (Format 4)
Note: If you change the station number setting, refer to 6-2-7 Communications Node Number
(3) Select Online - Write to PLC. A dialog box to write the set values will be displayed.

Table of Contents

Other manuals for Omron E5CC-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC-T and is the answer not in the manual?

Omron E5CC-T Specifications

General IconGeneral
BrandOmron
ModelE5CC-T
CategoryTemperature Controller
LanguageEnglish

Related product manuals