1 Communications Methods
1 - 6
E5@C Digital Temperature Controllers Communications Manual (H175)
E5@C-B (Models with Push-In Plus Terminal Blocks)
Abbreviation
Host
RS-485
AbbreviationPin
20
19
18
17
E5@C-B
RS-485
Shield
Terminating
resistance
120
Ω
(1/2 W)
6.8 V
TX
RX
Use 120
Ω (1/2 W)
terminating resistance.
Communications transceiver
Shield
E5@C-B
End node
RS-485
AbbreviationPin
20
19
18
17
A < B: “1” Mark
A > B: “0” Space
* Terminals 17 and 18 and terminals 19 and 20 are
connected internally. You can connect to either terminal.
FG
+
SG
A ()
A ()
B (+)
B (+)
A ()
A ()
B (+)
B (+)
Specify both ends of the transmission path
including the host as the end nodes (that
is, connect terminating resistance to both
ends). Use a terminating resistance of at
least 54
Ω.

Table of Contents

Other manuals for Omron E5CC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC and is the answer not in the manual?

Omron E5CC Specifications

General IconGeneral
Number of Display Digits4 digits
Number of Control Outputs1
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage, Analog current
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Display TypeLCD
Size48 x 48 mm
Mounting MethodPanel mount
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25% to 85% RH
Protection RatingIP66