6 - 73
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Advanced Function Setting Level
6
The alarm 1, 2, 3, or 4 output is prevented from turning ON until after the delay times set in these
parameters have elapsed.
a1on
Alarm 1 ON Delay
Alarm 1 must be assigned, and the alarm 1 type
must not be 0, 12, or 13.
a2on
Alarm 2 ON Delay
Alarm 2 must be assigned, and the alarm 2 type
must not be 0, 12, or 13.
a3on
Alarm 3 ON Delay
Alarm 3 must be assigned, and the alarm 3 type
must not be 0, 12, or 13.
a4on
Alarm 4 ON Delay
Alarm 4 must be assigned, and the alarm 4 type
must not be 0, 12, or 13.
Set the time for which the ON delay is to be enabled.
To disable the ON delay, set 0.
Related Parameters
Alarm 1 to 4 Type (Initial Setting Level): Page 6-48
Function
Setting
Setting range Unit Default
0 to 999 Seconds 0