Digital Temperature Controllers
User’s Manual
E5@C
H174-E1-14
Appendices
Index
Preparations
Introduction
Advanced
Operations
Basic
Operation
Part Names and
Basic Procedures
User Calibration
Parameters
1
2
3
4
5
6
7
A
I

Table of Contents

Other manuals for Omron E5CC

Questions and Answers

  • D
    Daniel RoySep 12, 2025
    How to set an end node for Omron E5CC Temperature Controller communication line?
    • R
      Ryan RodriguezSep 12, 2025
      If an end node has not been set at each end of the communications line on your Omron Temperature Controller, set or connect terminating resistance at each end of the line.
  • K
    Kim ChristianSep 9, 2025
    How long to wait before sending the next command to Omron Temperature Controller?
    • J
      James RobertsonSep 10, 2025
      If the host device sent the next command too soon after receiving a response from the Controller, wait for at least 2 ms after receiving a response before sending the next command.
  • K
    Kyle HuangSep 8, 2025
    What is the maximum number of devices for Omron Temperature Controller communication path?
    • R
      Ray LeeSep 8, 2025
      If too many communications devices are connected to the communications path on your Omron Temperature Controller, when 1:N, RS-485 communications are used, a maximum of 32 nodes may be connected, including the host node.
  • C
    Christian MartinSep 7, 2025
    What type of communication cable should I use for Omron E5CC Temperature Controller?
    • I
      Ian MartinSep 7, 2025
      If the wrong communications cable has been used for your Omron Temperature Controller, use shielded twisted-pair cable for the communications cable.
  • M
    Michelle MartinAug 23, 2025
    What to do if temperature error is large on Omron Controller (S.Err display)?
    • E
      Eric ThompsonAug 23, 2025
      If you are seeing a large temperature error or an S.Err display on your Omron Controller, it may indicate an input type mismatch. Check the sensor type and reset the input type correctly.
  • B
    brittanywilsonSep 5, 2025
    How to synchronize baud rate and communication method on Omron Temperature Controller?
    • D
      Dorothy ChenSep 5, 2025
      If the same baud rate and communications method are not being used by all of the Controllers, host devices, and other nodes on the same communications line, set the same values for the following on all nodes: baud rate, protocol, data length, stop bits, and parity.
  • J
    Jessica SheltonSep 4, 2025
    What to do if the Omron E5CC Temperature Controller communication cable is broken?
    • T
      Tina CookSep 4, 2025
      If the communications cable is broken on your Omron Temperature Controller, replace the cable.
  • C
    ckennedySep 3, 2025
    Why is the communication indicator on my Omron E5CC Temperature Controller PLC not lit?
    • A
      Alexander DavisSep 3, 2025
      If the communications indicator on the PLC is not lit, it could be due to several reasons: * The power supply is not turned ON to the E5@C Controller with communications unit number 0. * The wiring is not correct. * The communications settings are not the same between the PLC and the E5@C. * The E5@C was moved to the initial setting level (setting area 1). * Check the cycle time of the PLC. If it is longer than the value set for the Receive Data Wait Time parameter, change the set value of this parameter so that it is longer than the cycle time.
  • S
    Samuel ClarkSep 2, 2025
    What to do if the Omron Temperature Controller communication line is disconnected?
    • T
      tmckinneySep 2, 2025
      If the communications line has become disconnected on your Omron Temperature Controller, connect the communications line securely and tighten the screws.
  • L
    Leah JohnsonAug 31, 2025
    How to fix incorrect communications wiring on Omron Temperature Controller?
    • C
      Crystal MillerSep 1, 2025
      If the communications wiring is not correct on your Omron Temperature Controller, correct the wiring.

Summary

Digital Temperature Controllers Users Manual

Application Considerations

Safety Precautions

Precautions for Safe Use

Installation Precautions

Precautions for Operation

Preparations for Use

1-2 I;O Configuration and Model Number Legend

2 Preparations

2-1 Installation

Covers all aspects of physical installation, including dimensions and mounting.

2-2 Using the Terminals

Detailed guide on connecting wires to the terminal blocks for various models.

3 Part Names and Basic Procedures

4 Basic Operation

4-3 Setting the Input Type

Details how to configure the controller for different sensor inputs.

4-9 Determining PID Constants

Methods for calculating or setting PID control constants.

4-10 Alarm Outputs

Configuration of alarms using auxiliary outputs or control outputs.

5 Advanced Operations

5-3 Executing Heating;Cooling Control

Setting up and performing heating and cooling control operations.

5-7 Using the Key Protect Level

Securing the controller settings by restricting access via front panel keys.

5-11 Loop Burnout Alarm (LBA)

Detecting errors in the control loop, such as when the heater fails.

5-12 Performing Manual Control

Procedures for manually controlling the process variable.

6 Parameters

6-2 Protect Level

Details the four levels of protection for parameters and key operations.

6-4 Adjustment Level

Parameters for PID control, tuning, and heating/cooling adjustments.

6-7 Initial Setting Level

Basic setup parameters including input type, units, and control methods.

6-8 Advanced Function Setting Level

Parameters for advanced features like logic operations, alarms, and tuning.

7 User Calibration

A Appendices

A-4 Error Displays

Lists potential error codes and their meanings and remedies.

Omron E5CC Specifications

General IconGeneral
Number of Display Digits4 digits
Number of Control Outputs1
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage, Analog current
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Display TypeLCD
Size48 x 48 mm
Mounting MethodPanel mount
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25% to 85% RH
Protection RatingIP66

Related product manuals