Specifications
Ratings
Item AC100-240V type AC/DC24V type
Supply voltage AC100240V~, 50/60 Hz AC/DC24V~, 50/60 Hz
Power consumption 15 VA 6 VA, 3.5 W
Operating voltage range 85% to 110% of rated supply voltage
Input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: JPt100, Pt100
Current input: 4 to 20 mA, 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 1 to 10 V
Input impedance Current input: 150 W
Voltage input: 1 MW min.
Control output According to Output Unit (see “Output Unit Ratings and Characteristics” )
Auxiliary output SPST-NO, 1 A at 250 VAC (resistive load)
Control method ON/OFF or advanced PID control
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and LEDs
Other functions According to Option Unit (see “Option Unit Ratings and Characteristics” )