E5CK
E5CK
22
Terminal numbers9 and10 arefor controloutput 2(OUT2). Thethree outputtypes andinternal equalizingcircuits areavailable accordingtothe
Output Unit.
10
9
10
9
L
10
9
L
+V
+
-
+
-
GND
E53-Q4Q4 E53-Q4HQ4H
NPN PNP
E53-R4R4 /E53-V44R4
E53-Q4R4 /E53-C4R4
E53-Q4HR4/E53-C4DR4
Relay
+V
GND
The following table shows the specifications for each output type.
Output type Specifications
Relay
Voltage (NPN)
Voltage (PNP)
3 A at 250 VAC
20 mA at 12 VDC (with short-circuit protection)
20 mA at 12 VDC (with short-circuit protection)
0 to 10 V
4 to 20 mA
0 to 10 VDC, permissible load impedance: 1 kW min., resolution: approx. 2,600
4 to 20 mA, permissible load impedance: 500 W max., resolution: approx. 2,600
Auxiliary Output 1
Terminal numbers 2 and 3 are for auxiliary output 1 (SUB1).
The internal equalizing circuit for auxiliary output 1 is as follows:
5
4
3
2
1
10
9
8
7
6
13 14
11 12 3
2
Relay specifications are as follows:
SPST-NO, 250 VAC, 1 A
Option
Terminal numbers 1, 13, and 14 are valid only when the Option Unit is set in the Controller.
The following four connections are possible depending on the model of the Option Unit.
5
4
3
2
1
10
9
8
7
6
13 14
11 12
13
14
1
13
14
1
13
14
1
13
14
1
SD
RD
SG
A
B
+
4 to 20mA
E53-CK01
RS-232C
E53-CK03
RS-485
E53-CKB E53-CKF
Event input Transfer output
Use event inputs under the following conditions:
Contact input ON: 1 kW max., OFF: 100 kW min.
No-contact input ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
The polarity for no-contact input is as follows:
13
14
1
+
Transfer output specifications are as follows:
4 to 20 mA, load: 500 W max., resolution approx. 2600