E5CK
E5CK
5
Characteristics
Indication accuracy (see note) Thermocouple:
(±±0.3% of indication value or ±±1°°C, whichever greater) ±±1 digit max.
Platinum resistance thermometer:
(±±0.2% of indication value or ±±0.8°°C, whichever greater) ±±1 digit max.
Analog input: ±±0.2% FS ±±1 digit max.
Hysteresis 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) 0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I) 0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D) 0 to 3,999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1,999 to 9,999 or 199.9 or 999.9 (decimal point position dependent on input type)
Sampling period Temperature input: 250 ms
Analog input: 100 ms
Insulation resistance 20 MW min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance Malfunction: 10 to 55 Hz, 10 m/s
2
(approx. 1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s
2
(approx. 2G) for 2 hrs each in X, Y, and Z directions
Shock resistance Malfunction: 200 m/s
2
min. (approx. 20G), 3 times each in 6 directions
(100 m/s
2
(approx. 10G) applied to the relay)
Destruction: 300 m/s
2
min. (30G), 3 times each in 6 directions
Ambient temperature Operating: 10°°C to 55°°C (with no icing)/3-year warranty period: 10°°C to 50°°C
Storage: 25°°C to 65°°C (with no icing)
Ambient humidity Operating: 35% to 85%
Enclosure ratings Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory protection Non-volatile memory (number of writings: 100,000 operations)
Weight Approx. 170 g;
Adapter: approx. 10 g
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2:4kV contact discharge (level 2)
8kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10V/m (amplitude modulated, 80 MHz to
1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10V (0.15 to 80 MHz ) (level 3)
Immunity Burst: EN61000-4-4: 2kV power-line (level 3)
2kV I/O signal-line (level 4)
Approved standards UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/ part 100 (Finger Protection), when the separately-ordered terminal
cover is mounted.
Note: The indication accuracyof theK1, T, andN thermocouples ata temperature of -100°°C or lessis ±±2°°C ±±1digit maximum. Theindication
accuracy of the U, L1, and L2 thermocouples at any temperature is ±±2°°C ±±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°°C or less is ±±3°°C ±±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±±0.3% of the indicated value or ±±3°°C, whichever is greater)
±±1 digit maximum.
The indication accuracy of the PLII thermocouple at any temperature is (±±0.3% or ±±2°°C, whichever is greater) ±±1 digit maximum.
+/−
+/−
+/−
+/− +/−
+/− +/−
+/− +/−
+/−
+/−
+/−
+/− +/−
+/−
+/−
+/−
+/− +/−
+/− +/−
+/− +/−
+/−
+/−
+/−
+/− +/−