2.3 Detailed Description of the Services
2-11
Error Occurred
* For details on AT (auto-tuning), refer to the separate User’s Manuals.
(5) Precautions
● Alarm Function
Even though alarms are not displayed on the Controller’s display, they
function normally in communications.
Response code
Error name Cause
1002 Command too
short
The command is too short.
1101 Area type error The variable type is wrong.
1103 Start address out-
of-range error
Write start address is out of range.
1104 End address out-
of-range error
The write end address (write start
address + number of elements)
exceeds the final address of the vari-
able area.
1003 Number of ele-
ments/data mis-
match
The number of data does not match
the number of elements.
1100 Parameter error • Bit position is not “00.”
• The write data is out of the setting
range.
3003 Read-only error Variable type “C0” was written to.
2203 Operation error • The “communications writing”
parameter is set to “OFF” (dis-
abled).
• Write operation was performed on
the parameters from setup area 0
to setup area 1.
• Write operation was performed on
a protected parameter other than in
the protect level.
• AT (auto-tuning) was in progress.*
• EEPROM error