Event name Safety Unit Restore Operation Failed Event code 352B0000 hex
Meaning The restore operation for a Safety Unit ended in an error.
Source Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details NX Unit Detection tim-
ing
When Safety
Unit restoring
data is speci-
fied by the user
Error attrib-
utes
Level Observation Recovery --- Log category System
Effects User program Continues. Operation ---
System-de-
fined varia-
bles
Variable Data type Name
None None None
Cause and
correction
Assumed cause Correction Prevention
The SD Memory Card was re-
moved during a restore operation
for a Safety Unit.
Insert the SD Memory Card that
contains the Safety Unit Restore
File, cycle the power supply and
then perform the restore opera-
tion for a Safety Unit again.
Do not remove the SD Memory
Card during the restore operation
for a Safety Unit.
Data was read from or written to
the SD Memory Card via the
Support Software or an FTP cli-
ent during a restore operation for
a Safety Unit.
Store the correct Safety Unit Re-
store File to the SD Memory
Card, cycle the power supply and
then perform the restore opera-
tion for a Safety Unit again.
Do not read data from or write
data to the SD Memory Card via
the Support Software or an FTP
client during the restore opera-
tion for a Safety Unit.
Attached in-
formation
None
Precautions/
Remarks
None
l
Other Errors
12 Troubleshooting
12 - 65
NX-series Safety Control Unit User's Manual (Z930)
12-3 Checking for Errors with the Sysmac Studio
12
12-3-4 Error Descriptions