Event name Safety Process Data Communications Not Estab-
lished - Incorrect Unit Parameter Error
Event code 35210000 hex
Meaning Safety process data communications was not established with the Safety CPU Unit.
Source Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details NX Unit Detection tim-
ing
When safety
process data
communica-
tions are estab-
lished
Error attrib-
utes
Level Minor fault Recovery For request to
establish com-
munications
from Safety
CPU Unit after
removing
cause of error
Log category System
Effects User program Continues. Operation The Unit stops operating and the I/O data changes
to the safe states.
System-de-
fined varia-
bles
Variable Data type Name
None None None
Cause and
correction
Assumed cause Correction Prevention
The model or safety I/O terminal
settings are not correct.
Check the safety I/O terminal
settings, correct any errors, and
then transfer the settings to the
Safety CPU Unit.
Set the parameters considering
the corrections that are given on
the left.
Check the model of the Safety
I/O Unit to see if it is correct.
Attached in-
formation
None
Precautions/
Remarks
None
12 Troubleshooting
12 - 70
NX-series Safety Control Unit User's Manual (Z930)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX-SL3500 and is the answer not in the manual?

Omron NX-SL3500 Specifications

General IconGeneral
BrandOmron
ModelNX-SL3500
CategoryController
LanguageEnglish

Related product manuals