Event name I/O Power Supply Voltage Error Event code 65200000 hex
Meaning An incorrect I/O power supply voltage was detected.
Source Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details NX Unit Detection tim-
ing
During refresh-
ing
Error attrib-
utes
Level Minor fault Recovery When cause of
error is re-
moved
Log category System
Effects User program Continues. Operation The Unit continues to operate, but the I/O data re-
tains the safe states.
System-de-
fined varia-
bles
Variable Data type Name
None None None
Cause and
correction
Assumed cause Correction Prevention
The input power or output power
is not supplied correctly
.
Check the following and supply
the rated power.
• Is the power supply voltage
within the specifications?
• Is the wiring correct and not
disconnected?
• Is 24 V applied to the safety
output terminal and is the
safety output terminal not
touching the positive power
supply wire?
If the voltage that is measured is
correct, the Unit may be faulty
. In
that case, replace the CPU Unit.
Design the system considering
the corrections that are given on
the left.
Attached in-
formation
None
Precautions/
Remarks
None
12 Troubleshooting
12 - 80
NX-series Safety Control Unit User's Manual (Z930)