32
Remote I/O Terminal
SRT1-jD16T(-1)
Models with 3-tier Terminals (16 Points)
are Added to the Remote I/O Terminal
Series.
Six Models are Available Depending on
the NPN or PNP Configuration, Input
Points, I/O Points, or Output Points.
Incorporates
easy-to-wire terminals each connect
-
ing to a single wire.
Reduces designing and wiring effort.
Incorporates a removable circuit block of cassette
construction.
Ordering Information
I/O
classification
Internal I/O circuit
common
I/O points
I/O connection method
Model
Digital input
NPN (+ common)
16
M3 terminal block
SRT1-ID16T
PNP (+ common)
SRT1-OD16T-1
Specifications
Ratings
Inputs
Input
current
6 mA max./point at 24 V and 3 mA min./point at 17 V
ON delay time 1.5 ms max.
OFF delay time
1.5 ms max.
ON voltage
NPN: 15 VDC min. between V terminals and each input terminal
PNP: 15 VDC min. between G terminals and each input terminal
OFF voltage
NPN: 5 VDC max. between V terminals and each input terminal
PNP: 5 VDC max. between G terminals and each input terminal
OFF current
1 mA max.
Insulation method
Photocoupler
Outputs
Rated output current
0.5 A max./point
Residual voltage
1.2 V max.
ON delay time 0.5 ms max.
OFF delay time
1.0 ms max.
Leakage current
0.1 mA max.
Insulation method
Photocoupler