SRM1-C01-V2/C02-V2
SRM1-C01-V2/C02-V2
12
Communications Specifications
Communications
method CompoBus/S protocol
Coding method
Manchester coding method
Connection method
Multi-drop method and T
-branch method (see note 1)
Communications baud rate
750,000 bps/93,750 bps (see note 2)
Communications
cycle time
High-speed
comm nications
0.5 ms with 8 Slaves for inputs and 8 Slaves for outputs
cycle time
communications
mode
0.8 ms with 16 Slaves for inputs and 16 Slaves for outputs
Long-distance
comm nications
4.0 ms with 8 Slaves for inputs and 8 Slaves for outputs
communications
mode
6.0 ms with 16 Slaves for inputs and 16 Slaves for outputs
Communications cable
2-conductor VCTF cable (0.75 x 20)
Dedicated flat cable
Communications
distance
High-speed
communications
mode
VCTF cable:
Main line length:
100 m max.
Branch line length:
3 m max.
T
otal branch line length:
50 m max.
Flat cable:
Main line length:
30 m max.
Branch line length:
3 m max.
T
otal branch line length:
30 m max.
(When flat cable is used to connect fewer than 16 Slaves, the main line can be up to
100 m long and the total branch line length can be up to 50 m.)
Long-distance
communications
mode
VCTF cable:
Main line length:
500 m max.
Branch line length:
6 m max.
T
otal branch line length:
120 m max.
Max. number of connecting nodes
32
Error control checks
Manchester code check, frame length check, and parity check
Note: 1.
A terminator must be connected to the point in the system farthest from the Master
.
2.
The communications baud rate is switched using DM settings (default setting is 750,000 bps).
General Specifications
Supply
voltage
24 VDC
Allowable supply voltage
20.4 to 26.4 VDC
Power consumption
3.5 W max.
Inrush current
12.0 A max.
Noise immunity
Conforms to IEC61000-4-4, 2 kV (power lines)
V
ibration resistance
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
2
in X, Y
, and Z
directions for 80 minutes each
(T
ime coef
ficient; 8 minutes
×
coef
ficient factor 10 = total time 80 minutes)
Shock resistance
147 m/s
2
three times each in X, Y, and Z directions
Ambient temperature
Operating: 0
°
C to 55
°C
Storage: –20
°
C to 75
°C
Humidity
10% to 90% (with no condensation)
Atmosphere
Must be free from corrosive gas.
T
erminal screw size
M3
Power interrupt time
DC type: 2 ms min.
Weight
150 g max.