73
Analog Output Terminal
SRT2-DA02
Compact Analog Output Model is the
Same Shape as 16-point Remote I/O
Terminals
Two output points or 1 output point is selectable.
Resolution: 1/6,000
105 x 48 x 50 (W x H x D)
Ordering Information
Classification I/O
points
Model
Analog Output T
erminal
1 or 2 (selectable with DIP switch)
SRT2-DA02
Note: For
details about connecting the SRT2-DA02 to the Master Unit, refer to page
10.
Specifications
Ratings
Output
Item Voltage
output
Current output
External output permissible
load resistance
5 k
min. 600
max.
Output impedance
0.5
max.
---
Resolution
1/6,000 (FS)
Total
25°C ±
0.4% FS
Total
accuracy
–10 to 55
°C ±
0.8% FS
Conversion time
2 ms/2 points and 2 ms/1 point
Dielectric strength
500 V
AC for 1 min between communications power supply
, analog output, and communications terminals (see note)
Note: There
is no insulation between analog outputs.
Characteristics
Communications
power supply voltage
14 to 26.4 VDC (power supply possible from dedicated flat cable)
Current consumption (see note)
170 mA max.
Connection method
Multi-drop method and T
-branch method
Secondary branches cannot be connected to T
-branch lines.
Dielectric strength
500 V
AC (between insulated circuits)
Noise immunity
Conforms to IEC61000-4-4, 2 kV (power lines)
V
ibration resistance
10 to 150 Hz, 1.0-mm double amplitude or 70 m/s
2
Shock resistance
200 m/s
2
Mounting strength
No damage when 100 N pull load was applied in all directions
T
erminal strength
No damage when 100 N pull load was applied
Screw tightening torque
0.3 to 0.5 N
S
m
Ambient temperature
Operating: –10°
C to 55
°C
Storage: –25°
C to 65
°C
Ambient humidity
Operating:
25% to 85% (with no condensation)
Weight
Approx. 100 g
Note: The
above current consumption is the value with all points turned ON excluding the current consumption of the external load.