7-15
Constant
no.
SettingSetting rangeDescriptionIndi-
cators
n53 Frequency
detection level
0.0 to 400 (Hz) [0.0]
n54 Slip
compensation
gain
0.0 to 9.9 (%) [0.0]
n55 Motor current
with no load
0 to 99 (%) [40]
n56 Jump frequency
1
0.0 to 400 (Hz) [0.0]
n57 Jump frequency
2
0.0 to 400 (Hz) [0.0]
n58 Jump frequency
3
0.0 to 400 (Hz) [0.0]
n59 Jump width 0.0 to 25.5 (Hz) [1.0]
n60 Number of fault
retries
0 to 10 (times) [0]
n61 Stop Key
selection
0, 1 [0]
n62 Slip
compensation
primary delay
time
0.0 to 25.5 [2.0]
n63 UP/DOWN
command
frequency
memory
0, 1 [0]
n64 Operator’s
frequency
setting method
0, 1 [0]
Note 1. The upper limit of setting range and the factory settings for the 400-VAC-class
Inverters are double the above values.
Note 2. The setting range of the 400-VAC-class Inverter is “1 to 5.” The factory setting of
the 3G3EV-A4015M-CUE is “3.”
Note 3. Values in shaded sections or values in brackets represent factory settings.
Appendix A Chapter 7