2-8
H Installation Site
• Install the Inverter under the following conditions.
NEMA1 Type
Ambient temperature for operation: –10°C to 40°C
Humidity: 90% RH or less (no condensation)
Open Chassis Type
Ambient temperature for operation: –10°C to 45°C
Humidity: 90% RH or less (no condensation)
Note Remove the top and bottom covers when using the open chassis type of 15 kW or less.
• Install the Inverter in a clean location free from oil mist and dust. Alternatively, install it in a totally en-
closed panel that is completely shielded from floating dust.
• When installing or operating the Inverter, always take special care so that metal powder, oil, water, or
other foreign matter does not get into the Inverter.
• Do not install the Inverter on inflammable material such as wood.
H Ambient Temperature Control
• To enhance operation reliability, the Inverter should be installed in an environment free from extreme
temperature rises.
• If the Inverter is installed in an enclosed environment such as a box, use a cooling fan or air conditioner
to maintain the internal air temperature below 45°C.
H Protecting Inverter from Foreign Matter During Installation
• Place a cover over the Inverter during installation to shield it from metal powder produced by drilling.
• Upon completion of installation, always remove the cover from the Inverter. Otherwise, ventilation will
be affected, causing the Inverter to overheat.
Installation Chapter 2