3-4
General Specifications for 3G3HV Inverters
D 200-V Class
Model
3G3HV-j-CE
AB004 AB007 AB015 AB022 AB037
Maximum applica-
ble motor capacity
(kW)
0.4 0.75 1.5 2.2 3.7
Output characteristics
Rated output
capacity (kVA)
1.2 2.3 3.0 4.2 6.7
Rated output
current (A)
3.2 6 8 11 17.5
Maximum out-
put voltage (V)
3-phase, 200 to 230 VAC
(Corresponds to input voltage.)
Maximum out-
put frequency
(Hz)
400 Hz (Set by parameter constant.)
Power supply characteristics
Rated voltage
(V)
Rated frequen-
cy (Hz)
Single-phase, 200 to 230 VAC, 50/60 Hz
Allowable volt-
age fluctuation
–15% to 10%
Allowable fre-
quency fluctua-
tion
±5%
Heat generated
(kW)
0.07 0.09 0.12 0.14 0.22
Weight (kg)
Approx.
3
Approx.
4.5
Approx.
4.5
Approx.
6
Approx.
6
D 400-V Class
Model
3G3HV-j-CE
A4004 A4007 A4015 A4022 A4037 A4055 A4075 A4110 A4150 B4185 B4220 B4300 B4370 B4450 B4550 B4750 B411K B416K
Maximum applica-
ble motor capacity
(kW)
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 110 160
Output characteristics
Rated output
capacity (kVA)
1.4 2.6 3.7 4.7 6.1 11 14 21 26 31 40 50 61 73 98 130 170 230
Rated output
current (A)
1.8 3.4 4.8 6.2 8 14 18 27 34 41 52 65 80 96 128 165 224 302
Maximum out-
put voltage (V)
3-phase, 380 to 460 VAC (Corresponds to input voltage.)
Maximum out-
put frequency
(Hz)
400 Hz (Set by parameter constant.)
Power supply characteristics
Rated voltage
(V)
Rated frequen-
cy (Hz)
3-phase, 380 to 460 VAC, 50/60 Hz
Allowable volt-
age fluctuation
–15 to 10%
Allowable fre-
quency fluc-
tuation
±5%
Heat generated
(kW)
0.06 0.09 0.11 0.13 0.15 0.22 0.36 0.46 0.57 0.66 0.88 1.1 1.3 1.4 1.9 2.4 3.1 4.2
Weight (kg)
Approx.
3
Approx.
3
Approx.
4
Approx.
4.5
Approx.
4.5
Approx.
6.0
Approx.
6.0
Approx.
11
Approx.
11
Approx.
29
Approx.
31
Approx.
44
Approx.
44
Approx.
44
Approx.
81
Approx.
82
Approx.
135
Approx.
145
Specifications Chapter 3
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr